Flow Charts for Troubleshooting
SiAUY361411EA
143
Troubleshooting
15
Discharge Temperature Sensor Disconnected/
Shorted
Error
code
F6
Description
of the failure
Sub-code 0: While the unit is running, the outdoor air temperature is 10°C or higher but discharge
temperature 1 fails to rise above 0°C (which means that discharge temperature sensor 1 is
disconnected).
Sub-code 1: Discharge temperature 1 fails to rise above 0°C within 20 minutes after startup (which means
that discharge temperature sensor 1 is disconnected).
Sub-code 2: While the unit is running, discharge temperature 1 is reported as 201°C (which means that
discharge temperature sensor 1 is shorted).
Sub-code 3: While the unit is running, the outdoor air temperature is 10°C or higher but discharge
temperature 2 fails to rise above 0°C (which means that discharge temperature sensor 2 is
disconnected).
Sub-code 4: Discharge temperature 2 fails to rise above 0°C within 20 minutes after startup (which means
that discharge temperature sensor 2 is disconnected).
Sub-code 5: While the unit is running, discharge temperature 2 is reported as 201°C (which means that
discharge temperature sensor 2 is shorted).
Possible
causes
of the failure
Discharge temperature sensor failure; harness failure; main circuit board failure
Flow chart
NO
Check Discharge
Temperature Sensors.
025878-00E
Are Discharge Temperature
Sensors Operating Normally?
YES
Check whether the sensor is
connected properly to Main
Circuit Board's Harness.
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...