Inspecting the Outdoor Unit
SiAUY361411EA
179
Parts Inspection
1.6
Inspecting the Regulator
While blowing in air through the gas inlet, check the hole open to the atmosphere for any leaks.
(Submerge the regulator in water and check for any leaks based on whether air bubbles are
seen.)
1.7
Inspecting the Valve Clearance
1. With the bonnet cover removed, set the cylinder being tested to the top of the compression
stroke.
2. Measure the valve clearance using a thickness gauge.
Container
filled with water
Hole open to
the atmosphere
Gas inlet
Regulator
air
025947-00E
Measuring points
Set value
Standard valve clearance
0.25 to 0.35 mm
Valve
clearance
Valve rocker arm
Adjustment screw
Lock nut
010612-01E