SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
176
1.5
Inspecting the Ignition System
Output voltage
∗
This should be tested approximately 10 minutes after stopping (because the voltage
immediately after stopping will be the same as while running).
1. Using a tester, check if the output voltage requirements specified above are met.
2. If the voltage is significantly different than specified above, stop the system using the
onboard checker and wait for 5 minutes; then, with the power OFF, check the harness for
continuity and the junction connectors for contact failure using a tester.
3. If the harnesses and connectors are OK, then check each component.
Inspecting the ignition timing
• With the engine running, clip the plug cord of cylinder No.1 with the timing light clip. The timing
light will begin flashing. Point the flashing light to the flywheel circumference and you will be
able to determine the ignition timing of cylinder No.1 based on the position where the flywheel
tick mark comes to rest.
• Check the ignition timing of other cylinders by repeating this procedure.
[If the ignition timing significantly differs:]
• Check the crank pulse sensor and cam pulse sensor for any gap; the harnesses and
connectors for contact failure; and the signal lines for any noise due to their overlap with the
power supply lines.
• Make sure that the main CPU is correct for the current model.
[If the timing light fails to flash:]
If no problems are found after checking the above, replace the main circuit board and/or power
supply circuit board.
Parts to inspect
Measuring points
During
system
stop
∗
While system is running
(with actuator check
CH1 ON)
Ignition
power
supply
Primary side
Between starter transformer's
input terminals
0 V
200 V AC
Secondary
side
Between main circuit board's
CN20-5 and -6
0 V
14 V DC
Between power supply circuit
board's CN105-1 and -3
0 V
14 V AC
Between power supply circuit
board's CN107-1 and -2
0 V
14 V DC
Clip the ignition coil plug
cord.
Point the timing light to
the flywheel circumference.
025944-00E
TDC
bTDC10°
bTDC40°
1
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...