System Diagrams
SiAUY361411EA
21
Device Overview
5.1.5 Defrosting Operation
• High-temperature, high-pressure gas compressed by the compressor is fed via the solenoid
valve to the outdoor heat exchanger, which in turn condenses the gas while radiating the
condensation heat into the outdoor air. This condensation heat is used to melt frost formed on
the outdoor heat exchanger.
• The partially liquefied refrigerant that has passed through the outdoor heat exchanger is fed
via the receiver to the waste heat recovery device, where it completely evaporates and
deprives the gas engine cooling water (hot water) of heat before returning to the compressor.
The engine's waste heat is used as the heat source for heating operation.
GYEQ20AN
Waste heat
recovery
device
Accumulator
Receiver
Oil
cooler
Outdoor heat exchanger F
Outdoor heat exchanger B
Outdoor fan
Indoor unit
Indoor unit
Oil separator
Compressor 1
Compressor 2
BS unit
BS unit
(Intake gas)
(Discharge gas)
(Liquid)
PL
: Solenoid valves
: Electronic expansion valve
: Discharge temperature
: Intake temperature
: Oil temperature
: Check valve
: Stop valve
: High-side pressure switch
: High pressure sensor
: Low pressure sensor
SV
EV
TD
TS
TO
: Receiver temperature
TREC
CV
BV
HPS
PH
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...