Flow Charts for Troubleshooting
SiAUY361411EA
141
Troubleshooting
12
Outdoor Fan Failure
Error
code
F2
Description
of the failure
Sub-code 0: All fans fail to run within 60 seconds after they receive a Run command.
Possible
causes
of the failure
Fan failure; harness failure; DCBL circuit board failure; main circuit board failure
Flow chart
Is Outdoor Unit Supply
Voltage Normal?
YES
Use Correct Combination of
DCBL Circuit Board Connectors.
Fan 1
Fan 2
Fan 3
&1&1
&1&1
&1&1
Is Connector Combination
On Harness Appropriate?
YES
Is Voltage Across CN201-1
And -2 On DCBL Circuit Board
WR9'&"
YES
NO
Is Power Circuit Board's
CN104 Connected Properly To
DCBL Circuit Board's CN201?
YES
NO
NO
Check Supply Voltage.
NO
Correct Connector
Connections.
Change DCBL Circuit Board.
Change Power Supply
Circuit Board.
025875-01E