Receiver Temperature Sensor System Failure
Error
code
JF
Description
of the failure
Sub-code 0: While the unit is running, receiver temperature 31 is reported as 200°C (which means that
receiver temperature sensor 31 is disconnected).
Sub-code 1: While the unit is running, receiver temperature 31 is reported as 201°C (which means that
receiver temperature sensor 31 is shorted).
Possible
causes
of the failure
Receiver temperature sensor failure; harness failure; main circuit board failure
Flow chart
Is receiver temperature
sensor normal?
YES
NO
Inspect intake air
temperature sensor.
028037-00E
Check whether sensor
connected properly to Main
Circuit Board's Harness.