Flow Charts for Troubleshooting
SiAUY361411EA
129
Troubleshooting
2
Unit Runs But Does Not Cool
Flow chart
025862-00EN01
Unit Runs But Does Not Cool
Are You Sure
Failure Bypass Control
Is Not Activated?
Is Compressor
Intake/Discharge Pressure
Normal?
Is the four-way valve
operating normally?
Are the SV3A-3F and SV31
operating normally?
Are Outdoor Unit EVs
and SVs Operating Normally?
Is Recharged Refrigerant
Amount Proper?
Are Indoor Unit Fans
Operating Normally?
Is the wiring between the
outdoor unit/indoor unit/BS unit
operating normally?
Is the piping between the
outdoor unit/indoor unit/BS unit
operating normally?
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Change Temperature
Set-Point.
Check Failure Bypass
Control Conditions.
See “Standard Operation
Data List.”
Four-way valve/SV inspection
Check EVs and SVs.
Check Recharged
Refrigerant Amount.
Check Indoor Unit Fans.
Check Cables For Defects.
Check Pipes.
YES
YES
NO
Check the external filter.
Is Cooling Set
Temperature Lower
Than Room
Temperature?
Please contact your Daikin
(Yanmar) representative if
you can not find the cause
even after you have checked
all the items down to the
bottom of the flowchart.
Is the external filter free
of defects?
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...