Installation Work Manual
SiAUY361411EA
37
Device Overview
0FGHP-EN0801 DGJ002
–
9
–
7 Installing the Outdoor Unit
Bringing the outdoor unit into the room
z
Decide in advance how you will transport the product to its installation location.
z
Follow the instructions on how to transport the outdoor unit indicated on the paper attached to the
front face of the outdoor unit.
Preparing the refrigerant piping
Any tools and instruments used to handle the refrigerant and the refrigerating machine oil during installation
work should be designed specifically for use with the R410A.
Piping materials
The refrigerant piping used should be made of the following material:
z
Material:
Phosphate deoxidized seamless copper tube
Pipe size
Selecting the correct pipe size
z
Piping between the outdoor unit and refrigerant branch kit
The size of the pipes used should match the outdoor unit's
pipe size.
When you use long pipes (with an equivalent length of 90
m or greater), you can use a gas pipe that is one size
larger than the pipe diameter indicated in the table on the
right hand to minimize loss of cooling performance due to
the pipe length. (Reducer joints should be locally procured
if needed.) However, only when the outdoor unit is installed
in a location higher than the indoor unit with a height
difference more than 50 m but less than 70 m, using a gas
pipe that is one size larger than the pipe diameter to
minimize the loss of performance with long pipes is not
possible.
Size
ij
ij
ij
ij
ij
ij
ij
ij
ij
ij
Wall thickness
t0.8
t0.8
t0.8
t1.0
t1.0
t1.0
t1.0
t1.0
t1.1
t1.4
Outdoor
unit
capacity
Pipe size (outside diameter x minimum wall
thickness) (in mm)
Suction gas
pipe
Discharge
gas pipe
Fluid pipe
GYEQ20AN
ij[W ij[W ij[W
GYEQ30AN
ij[W ij[W ij[W
7
Installing the Outdoor Unit
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...