SiAUY361411EA
Actuator Control
Control and Functionality
104
[Cooling main, heating main A]
• Keeps SH at the SC receiver outlet at a constant level.
• When the low-side pressure is lower than the low-side pressure set-point, keeps the low-side
pressure at a constant level.
[Heating, heating main B]
• Keeps SH at the SC receiver outlet at a constant level.
• These valves are normally controlled to the target of SH3 = 20°C so that refrigerant flows into
the waste heat recovery heat exchanger at an optimal flow rate.
• When the discharge temperature exceeds 100°C, these valves are controlled to the minimum
target of SH = 7°C.
EV5
[Cooling]
• When the engine is running at the minimum speed and yet the low-side pressure is lower than
the low-side pressure set-point, the waste heat recovery heat exchanger is used as an
evaporator. In this case, the opening degrees of these valves are adjusted to keep the low-
side pressure at a constant level.
[Cooling main, heating main A]
• When the low-side pressure is lower than the low-side pressure set-point, keeps the low-side
pressure at a constant level.
[Heating, heating main B]
• These valves are normally controlled to the target of SHS3 = 20°C so that refrigerant flows
into the waste heat recovery heat exchanger at an optimal flow rate.
• When the discharge temperature exceeds 100°C, these valves are controlled to the minimum
target of SHS5 = 7°C.
EV6
[All modes]
• Adjusts the compressor oil return temperature to the optimal value.
EV7
[Heating, heating main B]
• When the fluid pressure is higher than the fluid pressure set-point, adjusts the fluid pressure
by making the receiver gas flow to the low pressure side.
EV3A
[Cooling, cooling main, heating main A]
• If the high pressure cannot be maintained at the pressure set-point, synchronizes with SV3A
and 3B to maintain the high pressure.
EV3B
[Cooling main, heating main A, heating, heating main B]
• When the fluid pressure drops and reduced performance of the cooling indoor unit occurs,
maintains the receiver outlet pressure.
MV (water motor-operated valve)
[Cooling, cooling main, heating main A, heating, heating main B]
• Adjusts the evaporation amount by setting the refrigerant amount that flows into the waste
heat recovery heat exchanger to the optimal level.
SV1
[Cooling]
• This valve is closed (turned OFF).
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...