Flow Charts for Troubleshooting
Troubleshooting
152
25
Outdoor Air Temperature Sensor Disconnected/
Shorted
Error
code
J3
Description
of the failure
Sub-code 0: While the unit is running, the outdoor air temperature is reported as 200°C (which means that the
outdoor air temperature sensor is disconnected).
Sub-code 1: While the unit is running, the outdoor air temperature is reported as 201°C (which means that the
outdoor air temperature sensor is shorted).
Possible
causes
of the failure
Outdoor air temperature sensor failure; harness failure; main circuit board failure
Flow chart
NO
Check Outdoor Air
Temperature Sensor.
025892-00E
Is Outdoor Air Temperature
Sensor Operating Normally?
YES
Check whether sensor
connected properly to Main
Circuit Board's Harness.