Inspecting the Outdoor Unit
SiAUY361411EA
173
Parts Inspection
1.3
Inspecting the Fuel Control System
Output voltage
Inspecting the gas solenoid valves
Inspect the gas solenoid valves by measuring the resistance between their terminals.
Parts to inspect
Measuring points
During system
stop
While system running
(with actuator check ON)
Gas solenoid
valve 1
Between main circuit board's
CN9-1 and -4
0 V
CH03
12 V DC
Gas solenoid
valve 2
Between main circuit board's
CN9-3 and -5
0 V
CH04
12 V DC
Measuring points
Measured value
Between gas solenoid valve terminals
16.7
Ω