SiAUY361411EA
Test Run Manual
Device Overview
80
0FGHP-EN0841 DGJ002
–
13
–
2 How to Perform a Test Run
2. Special operation
(1) Enter RUN mode, select CH [2] at level 1 and press NEXT . (2) Select the CH of the desired mode
(refer to the table below) at Level 2 and press NEXT . (3) Change the set value as ON/OFF using UP
and DOWN , and then press ENTER for setting. If ENTER is pressed again, the setting becomes
inactive.
(A valid setting is constantly lit. An invalid setting blinks.)
Once the settings are valid, they do not become invalid unless they are changed manually or the checker is stopped
to display the total operated hours.
Ƒ7DEOH/LVWRIVSHFLDORSHUDWLRQPRGHVHWWLQJV
CH
Item
Content
01
Forced thermostat designation
ON/OFF
02
Checker mode designation
OFF: auto, ON: checker mode
03
Operation mode designation
OFF: auto mode, ON: manual mode
04
Actual engine speed
Minimum speed to maximum speed (min
-1
)
Setting is available only in manual
mode.
05
Clutch 1
ON/OFF
06
Clutch 2
ON/OFF
07/08
Vacant
09
Coolant air bleed operation (Note 1)
10
Pump down for maintenance (Note 1)
ON/OFF
Only one of the functions can be
turned on at a time.
11
Refrigerant Misfilling Emergency Mode (Note 1) ON/OFF
12/13
Vacant
14
Refrigerant Additional Filling Mode (Note 1)
ON/OFF
15/16
Vacant
Note 1: Power reset is required after the operation is terminated (OFF).
3. Indoor unit
3-1. Indoor Unit Information Display
(1) Enter RUN mode, select CH [3] at Level 1 and press NEXT . (2) Select CH [01] at Level 2 and press
NEXT . (3) Select the desired indoor unit No. at Level 3 and press NEXT . (4) When selecting the CH
(refer to the table below) of the desired data at Level 4, the data is displayed.
Ƒ7DEOH/LVWRI,QGRRU8QLW'DWD
CH
Item
Content
CH
Item
Content
01
Indoor unit No.
0: Communication not established; 1 to
64: indoor unit No.
09
Indoor unit capacity
02
Number of running
indoor units
3rd and 4th digits: number of units with
thermostat ON
3rd and 4th digits: number of running
indoor units
10
Electronic expansion
valve
Pulse
11
Vacant
03
RUN mode
3rd digit: temperature control mode
H: heating, C: cooling, d: dehumidification, 0: blowing
2nd digit: thermostat ON (1) / OFF (0)
1st digit: run (1) / stop (0)
12
Communication status
N u m b e r o f i n d o o r
units display
3rd and 4th digits: communication status
1st and 2nd digits: number of connected
indoor units
13
BS address
04
Error code
14
BS mode
0: initial status
1: cooling
2: heating
3: switching from cooling to heating
4: switching from heating to cooling
05
Set temperature
°C
06
Fluid pipe
temperature
°C
07
Gas pipe
temperature
°C
08
Intake
Temperature
°C
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...