SiAUY361411EA
Installation Work Manual
Device Overview
52
0FGHP-EN0801 DGJ002
–
24
–
7 Installing the Outdoor Unit
Normal vacuum drying
(1) Vacuum
drying:
Evacuate the piping from the fluid and gas (both intake gas and discharge gas for AFZP
models) sides of the outdoor unit's closing valve as well as from the servicing port. If a
negative pressure of -0.101 MPa or less is attained during continuous evacuation for
two hours or longer, then the vacuum drying process is complete.
- If a negative pressure of -0.101 MPa or less cannot be attained, continue evacuation
for one additional hour.
- If a negative pressure of -0.101 MPa or less cannot be attained over three hours,
conduct the air tightness test again.
(2) Vacuum
retention test:
After evacuating the piping to -0.101 MPa or less, leave it for one hour. If the gauge
reading is retained for one hour, then the vacuum retention test is successful.
- If the gauge reading has risen, chances are that there is moisture remaining inside the
piping or a leak exists. If this is the case, perform the special vacuum drying process
(described below) or conduct the air tightness test again.
Special vacuum drying
If there is a possibility of water invasion into the piping as is the case with piping work that takes a long
period of time or that is done during a rainy season, perform the special vacuum drying process described
below:
Vacuum break: Using nitrogen gas, pressurize the piping to 0.0490 MPa.
(1) Vacuum drying
ʊĺ
(2) Vacuum break (N
2:
0.0490MPa
ʊĺ
(3) Vacuum drying (1 hour)
Ň
'HJUHHRIYDFXXPUHDFKHV03DRUORZHUĸŋ
Ň
NO
Ň
YES
Ļ
Ļĸ
――――――――――――
ʼn
Vacuum drying for two additional hours
(4) Vacuum retention test
Ň
Ň
Ň
ŋ
Ļ
Degree of vacuum reaches -0.101 MPa
――
Ň
NO
Ļ
YES
Air tightness test again
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...