SiAUY361411EA
Outdoor Unit Control
Control and Functionality
100
(Heating) "Overload Capacity" control function
[1.1 System Control Overview]
See the
Basic heating control
section.
(Heating) "Inhibit Operation under Overload" control function
When the outdoor air temperature rises to 26°C or higher during heating and the "Overload
Capacity" control function (for heating) cannot control high-side pressure 1, this function is
activated to lower the operable range of outside air temperatures by temporarily stopping the
outdoor unit.
(Cooling/heating) This control function determines the outside air temperature threshold (35°C
to 26°C) for the "Inhibit" control function (for cooling/heating) to be activated.
(Heating) "Defrost" control function
When the outdoor heat exchanger is frosted and its temperature drops, this function is activated
to defrost the heat exchanger by turning ON SV3A/3B/3C/3D and turning OFF SV3E/3F so that
gas is discharged.
• Activation conditions
The control function is activated when intake temperature 1 is lower than -3°C and the
difference between the outdoor air temperature and intake temperature 1 stays constant for
10 minutes or longer.
• Deactivation conditions
When the specified time period or longer has elapsed after turning ON SV3A/3B/3C/3D and
turning OFF SV3E/3F or when high-side pressure 1 has risen to the specified pressure or
higher, the defrosting process is complete, and SV3A/3B/3C/3D are returned to the OFF
position and SV3E/3F are returned to the ON position.
(Heating) "Enhance Performance at Low Outdoor Air Temperatures" control function
When the number of engine speed steps is the maximum standard value, high-side pressure 1
is equal to or lower than the high-side pressure set point, and the outdoor air temperature is 6°C
or lower, this function is activated to enhance heating performance by increasing the number of
engine speed steps.
(Heating) "Avoid High-Side Pressure Rise during Transition" control function
[1.1 System Control Overview]
See the
Basic heating control
section.
(Heating) "Oil Return" control function
1 hour after starting the outdoor unit and at every cumulative 8 hours after this, or when the oil
separator oil level is at or below the detection level, this function sets the outdoor unit circuit and
BS circuit to the cooling circuit and performs the oil return operation.
(Heating) "Indoor Unit Refrigerant Recovery" control function
If refrigerant accumulates in an inactive indoor unit, this function increase the expansion valve
opening degree to perform a refrigerant recovery operation.
(Cooling) (Heating) "Energy Saving Mode" control function
You can select the energy saving mode by configuring the memory switches with the onboard
checker of the main circuit board as shown in the table below. The energy saving mode works
by restricting the engine speed upper limit to reduce gas consumption regardless of whether the
load is low or high.
[Note]
Cooling/heating performance is more or less sacrificed when energy saving mode is
configured, possibly resulting in "Cannot Get Cool/Warm" complaints from end users.
[Configuring the energy saving mode]
Memory switch
Normal operation mode
Energy saving mode
Cooling
CH4-No.4
OFF
ON
Heating
CH4-No.6
OFF
ON
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...