Control Overview
SiAUY361411EA
95
Control and Functionality
1.3
Actuators
Table 3.3/ Operation of each actuator
Name
Cooling
dehumidi-
fication
Heating
Concurrent
cooling/
heating
Blowing Defrosting
Thermo-
OFF
Operation
-OFF
System
stop
Remarks
Gas 1 & 2
{
{
{
—
{
∆
—
Fuel control valve
∆
∆
∆
—
∆
∆
—
Throttle valve
∆
∆
∆
—
∆
∆
—
Fans 1, 2 & 3
∆
∆
∆
—
∆
∆
—
Cooling water pump
{
{
{
—
{
∆
—
Four-way valve 1
∆
—
—
—
—
∆
∆
Normal
heating
EV1 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
—
EV2 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
—
EV3 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
∆
EV4 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
—
EV5 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
—
EV6 (outdoor electronic expansion valve)
∆
∆
∆
—
∆
∆
—
EV7 (outdoor electronic expansion valve)
—
∆
∆
—
—
—
—
EV3A (outdoor electronic expansion valve)
—
—
∆
—
∆
—
—
EV3B (outdoor electronic expansion valve)
—
—
∆
—
∆
—
∆
Clutches 1 & 2
∆
∆
∆
—
∆
∆
—
Compressor heaters 1 & 2
—
—
—
{
—
—
{
Oil separator heater
—
—
—
∆
—
—
∆
Accumulator heater
—
—
—
∆
—
—
∆
Oil return heater
—
—
—
{
—
—
{
SV1 (solenoid valve)
—
∆
∆
—
∆
∆
—
SV2 (solenoid valve)
∆
∆
—
—
∆
∆
—
SV3 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV4 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV6 (solenoid valve)
∆
—
—
—
—
∆
—
SV7 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV8 (solenoid valve)
—
∆
∆
—
—
—
—
SV9 (solenoid valve)
∆
∆
∆
—
—
∆
—
SV10 (solenoid valve)
∆
—
—
—
—
∆
—
SV12 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV31 (solenoid valve)
∆
∆
∆
—
∆
∆
—
Normally
open
SV32 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV37 (solenoid valve)
∆
∆
∆
—
∆
∆
—
SV3A (solenoid valve)
∆
—
∆
—
∆
∆
∆
SV3B (solenoid valve)
∆
—
∆
—
∆
∆
∆
SV3C (solenoid valve)
∆
—
∆
—
∆
∆
∆
SV3D (solenoid valve)
∆
—
∆
—
∆
∆
∆
SV3E (solenoid valve)
—
∆
∆
—
∆
∆
∆
SV3F (solenoid valve)
—
∆
∆
—
∆
∆
∆
SV3G (solenoid valve)
∆
—
∆
—
∆
∆
—
SV3H (solenoid valve)
∆
—
∆
—
∆
∆
—
{
: Normally ON
∆
: Turned ON/OFF or opening degree varied by the control function specific to that actuator -: Normally OFF
Thermo-OFF/operation-OFF: Outdoor unit is in pump down operation.
System stop: Outdoor unit is stopped (including stop of outdoor unit due to thermo-OFF).
∗
Whether each of the actuators listed exists depends on the model and version.
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...