Flow Charts for Troubleshooting
SiAUY361411EA
161
Troubleshooting
35
Abnormal Exhaust Temperature
Error
code
L1
Description
of the failure
Sub-code 0: While the unit is running, the exhaust temperature rises to or above 650°C.
Possible
causes
of the failure
Misfire (ignition system failure); mixer failure; fuel gas type setting incorrect; engine oil up; engine oil down;
exhaust temperature sensor failure; engine cooling failure; flammable gas contained in intake air;
catalyst failure; harness failure; main circuit board failure
Flow chart
Is Exhaust Temperature Sensor
Operating Normally?
YES
YES
Is Fuel Gas Type
Setting Correct?
Is Ignition System
Operating Normally?
YES
Is Engine Cooling Water
System Operating Normally?
YES
Is Mixer Operating Normally?
YES
NO
Check Ignition System.
NO
Configure Main Circuit Board.
NO
Check Exhaust
Temperature Sensor.
YES
Is Engine Compression
Pressure Normal?
YES
Is Oil Level Normal?
YES
NO
Check Engine Compression
Pressure.
Is Engine Oil Consumption
Normal?
YES
Is Valve Clearance Appropriate?
NO
Check Mixer.
NO
See Flow Chart In
"Abnormal Cooling Water
Temperature" Section.
Check Valve Clearance.
NO
NO
Check Oil Level.
NO
Check Oil Consumption.
YES
Is Sensor Connected
Properly To Main Circuit
Breaker's Harness?
NO
Check Electrical
Wiring System.
025902-00E
Check whether engine
suctioned Inflammable Gas.
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...