Flow Charts for Troubleshooting
SiAUY361411EA
151
Troubleshooting
23
Air-Fuel Ratio Controller Failure
Error
code
J1
Description
of the failure
Sub-code 0: While the unit is running, the air-fuel ratio controller does not function properly.
Sub-code 1: While the unit is running, the following conditions continue for 3 minutes: 1) the throttle valve
opening degree is equal to or lower than 500 pulses; 2) the current speed is equal to or lower
than 1150 min
-1
; 3) the current speed is equal to or lower than the target speed minus 100 min
-1
.
Possible
causes
of the failure
Mixer malfunction
Flow chart
Check Mixer.
025890-00E
24
Intake Air Temperature Sensor 1 Disconnected /
Shorted
Error
code
J2
Description
of the failure
Sub-code 0: While the unit is running, intake air temperature 1 is reported to be equal to 200°C (which means
that intake air temperature sensor 1 is disconnected).
Sub-code 1: While the unit is running, intake air temperature 1 is reported as 201°C (which means that intake
air temperature sensor 1 is shorted).
Sub-code 2: While the unit is running, intake air temperature 2 is reported as 200°C (which means that intake
air temperature sensor 2 is disconnected).
Sub-code 3: While the unit is running, intake air temperature 2 is reported as 201°C (which means that intake
air temperature sensor 2 is shorted).
Sub-code 4: While the unit is running, intake air temperature 3 is reported as 200°C (which means that intake
air temperature sensor 3 is disconnected).
Sub-code 5: While the unit is running, intake air temperature 3 is reported as 201°C (which means that intake
air temperature sensor 3 is shorted).
Sub-code 6: While the unit is running, intake air temperature 4 is reported as 200°C (which means that intake
air temperature sensor 4 is disconnected).
Sub-code 7: While the unit is running, intake air temperature 4 is reported as 201°C (which means that intake
air temperature sensor 4 is shorted).
Sub-code 8: While the unit is running, intake air temperature 5 is reported as 200°C (which means that intake
air temperature sensor 5 is disconnected).
Sub-code 9: While the unit is running, intake air temperature 5 is reported as 201°C (which means that intake
air temperature sensor 5 is shorted).
Possible
causes
of the failure
Intake air temperature sensor failure; harness failure; main circuit board failure; sub circuit board failure
Flow chart
NO
Check Intake
Air Temperature Sensor.
025891-00E01
Is Intake Air Temperature
Sensor Operating Normally?
YES
Check whether sensor
connected properly to Main
Circuit Board's and Sub-
Circuit Board's Harnesses.
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...