Troubleshooting the Outdoor Unit
SiAUY361411EA
123
Troubleshooting
1.4.3 Configure Items
ON/OFF unit (memory switch)
(1) Enter STOP mode, select CH [3] in Level 1 and press
. (2) Select CH [01] in Level
2 and press
. (3) Select the CH
(Table 4.12)
of the item you want to change in Level 3
and press
. (4) Select the number
(Table 4.12)
of the item you want to change in
Level 4 and press
. (5) Change the ON/OFF value using
and
, then
press
to save the new value.
For CH55, No. 1, 2 and 3 are cleared when you set the value to "ON" and they are reset to OFF
when you exit from STOP mode after setting them to ON. However, this does not mean the
clear setting is disabled.
Reset the power supply after changing the settings.
Table 4.12/ (List of ON/OFF unit items)
∗
If your selected channel contains an item that is not supported by the unit model, the LCD
displays nothing or "-".
∗
Items not listed above are not used. Do not attempt to change any unlisted settings.
(Note 1)Cooling/heating performance is more or less sacrificed for the quiet mode or energy
saving mode, possibly resulting in "Cannot Get Cool/Warm" complaints from end users.
(Note 2)The GVM aging correction amount is cleared at the same time.
(Note 3)Be careful that the outdoor fan may turn while the unit is stopped.
(Note 4)Set when the outdoor unit is installed in a location higher than the indoor unit, the
difference in levels between the indoor units is 9 m or higher, and the ratio of the bottom
indoor unit is 50% or less.
NEXT
NEXT
NEXT
NEXT
UP
DOWN
ENTER
CH No.
Item
Content
01
3
Support for facility-use/
outdoor air processing
indoor unit
ON: when connecting a facility-use/outdoor air processing indoor unit /
OFF: normal (factory default: OFF)
4
Quiet cooling mode
(Note 1)
OFF
Normal operation
mode
(factory default)
ON
Quiet mode
operation
ON
Super-quiet mode operation
5
OFF
OFF
ON
6
Quiet heating mode
(Note 1)
OFF
Normal operation
mode
(factory default)
ON
Quiet mode
operation
ON
Super-quiet mode operation
7
OFF
OFF
ON
02
7
Quiet mode external
signal
ON: quiet mode turned ON/OFF via an external signal (option) / OFF: normal (factory
default: OFF)
03
3
High static pressure
support
ON: enabled / OFF: disabled (factory default: OFF)
04
4
Energy saving cooling
mode (Note 1)
ON: enabled / OFF: disabled (factory default: OFF)
6
Energy saving heating
mode (Note 1)
ON: enabled / OFF: disabled (factory default: OFF)
09
0
Defrosting
OFF
Normal defrosting
(factory default)
ON
Reinforced defr stop
defrosting
OFF Stop defrosting
only
1
OFF
OFF
ON
2
Reinforced defrosting
interval
OFF
4 hours
(factory default)
ON
Always not
established
OFF
2 hours
ON
8 hours
3
OFF
OFF
ON
ON
10
2
Air Guard setting
OFF: no / ON: yes (factory default: OFF)
4
Heating eccentric flow
setting (Note 4)
OFF: disabled / ON: enabled (factory default: OFF)
13
4
Periodic inspection
reminder
OFF Reminder: ON /
Energy saving: ON
(factory default)
ON
Reminder: OFF
Energy saving:
OFF
OFF Reminder: ON
Energy saving:
OFF
ON
Do not use this
setting.
5
OFF
OFF
ON
ON
14
0
Snow sensor support
(Note 3)
OFF: disabled / ON: enabled (factory default: OFF)
1
Snow sensor wait time
setting (in minutes)
OFF
50
(factory default)
ON
30
OFF
20
ON
10
2
OFF
OFF
ON
ON
55
1
Clear GVM initial
correction amount
ON: clear / OFF: normal (normally OFF: turned ON only when clearing the value.)
2
Clear GVM aging
correction amount
ON: clear / OFF: normal (normally OFF: turned ON only when clearing the value.)
3
Clear elapsed time
since last maintenance
(Note 2)
ON: clear / OFF: normal (normally OFF: turned ON only when clearing the value.)
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...