Troubleshooting the Outdoor Unit
Troubleshooting
116
1.3.1 Outdoor Units
Outdoor unit data display
(1) Enter RUN mode, select CH [1] in Level 1 and press
. (2) Select CH [01] in Level
2 and press
. (3) When the CH
(Table 4.4)
of the desired data item is selected in
Level 3, the data is displayed.
Table 4.4/ (List of outdoor unit data)
∗
If your selected channel contains an item that is not supported by the unit model, the LCD
displays nothing or "-".
Fig. 4.5/ (Content of outdoor unit segment display)
NEXT
NEXT
CH
Item
Content
CH
Item
Content
01
Current speed
min
-1
35
Circuit board temperature
°C
02
Target speed
min
-1
36
Not used
03
Speed set-point
min
-1
37
(Reserved for future use)
04
Throttle valve
pulse
38
(Reserved for future use)
05
Fuel control valve
pulse
39
Not used
06
Mode-flag
4th digit: 0, normal
mode; 1, checker mode
40
(Reserved for future use)
3rd digit: 0, stop; 1,
operation
41
Not used
2nd digit: 0, blowing; H,
heating; C, cooling
42
Not used
1st digit: 0, auto; 2,
manual
43
Not used
07
EV1
pulse
44
SHS1
°C
08
EV2
pulse
45
SHS2
°C
09
EV3
pulse
46
SHS3
°C
10
EV4
pulse
47
SHS4
°C
11
EV5
pulse
48
SHD1
°C
12
EV6
pulse
49
SHD2
°C
13
Water motor valve
pulse
50
SHO1
°C
14
Fan 1
min
-1
51
SHO2
°C
15
Fan 2
min
-1
52
(Reserved for future use)
16
Fan 3
min
-1
53
High pressure converted temperature 1
°C
17
Cooling water pump
min
-1
54
(Reserved for future use)
18
Cooling water temperature
°C
55
Low pressure converted temperature
°C
19
High-side pressure 1
MPa
56-59 Not used
20
Low-side pressure
MPa
60
Receiver temperature 31
°C
21
Outdoor air temperature
°C
61
Intake temperature 5
°C
22
Exhaust temperature
°C
62
Oil temperature 3
°C
23
Discharge temperature 1
°C
63
Oil temperature 4
°C
24
Discharge temperature 2
°C
64
(Reserved for future use)
25
Intake temperature 1
°C
65
SHS5
°C
26
Intake temperature 2
°C
66
SHO3
°C
27
Intake temperature 3
°C
67
SHO4
°C
28
Intake temperature 4
°C
68
(Reserved for future use)
29
Oil temperature 1
°C
69
High-side pressure 2
MPa
30
Oil temperature 2
°C
70
High-side pressure 3
MPa
31
(Reserved for future use)
71
High-side pressure 4
MPa
32
(Reserved for future use)
72
EV3A
pulse
33
(Reserved for future use)
73
EV3B
pulse
34
(Reserved for future use)
74
EV7
pulse
Segment 0
Segment 5
Segment 4
Segment 3
Segment 2
Segment 1
CH number display
Actuator status display
4th digit
3rd digit
2nd digit
1st digit
022708-00E
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...