Wiring Manual
SiAUY361411EA
63
Device Overview
a
0FGHP-EN0821 DGJ002
–
6
–
3. Setting and Rewiring the Outdoor Unit
Configuring the Outdoor Unit DIP Switches
CAUTION
z
Before accessing the DIP switches, turn off the power and make sure that none of
the LEDs on the circuit board are lit. Attempting to access the DIP switches with
any LED lit could result in an electrical shock due to electricity remaining in the
circuit.
Be sure to check the DIP switch settings whether or not you want to change the factory default settings.
After changing any DIP switch setting or connector, you have to turn the power off and back on for the
new setting to take effect.
When you want to reset the outdoor unit power supply, turn off the power and make sure that none of the
LEDs on the circuit board are lit before turning back on the power. An attempt to reset the power supply
with any LED lit may fail due to electricity remaining in the circuit.
Configuring the DIP switches on the main circuit board
z
Use the following tables to check/configure the DIP switches:
Name
SW
No.
Parameter
Description
Factory
default
On-site
configuration
Remarks
DSW1
Õ
Piping length
(equivalent length)
1
2
1: off
2: off
Required
off
off
Piping length is 30 m or less.
on
off
Piping length is between 30 m and 80 m.
off
on
Piping length is between 80 m and 130 m.
on
on
Piping length is 130 m or more.
Õ
Heating temperature
level
3
4
3: off
4: off
Configure
when
required.
off
off
Heating temperature level is set to
"Standard".
on
off
Heating temperature level is set to "Low".
off
on
Heating temperature level is set to "High".
on
on
Heating temperature level is set to "Outdoor
Air Temperature Processing".
Cooling/heating
selection priority
on
Priority to the indoor unit (remote controller)
on
Configure
when
required.
Be sure to set the switch on.
off
Priority to the outdoor unit
Õ
Fuel gas type
6
7
8
Factory
default
Depending on
specification
Confirmation
only
off
off
off
Natural gas
3
. Setting and Rewiring the Outdoor Unit
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...