Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
69
EXT LOAD
REQUEST
IS-AIN8
IG/IS-NT
CAN 1
VAO
LAI
(PMS: AnExSysBld)
EXTERNAL
G
IG/IS-NT
VAI
LAI
(PMS: AnExSysBld)
EXTERNAL
IG/IS-NT
VAI
LAI
(PMS: AnExSysBld)
EXTERNAL
G
G
Derating1 strt
[ X ] (FV)
Derating2 strt
[ X ] (FV)
The starting values for the power derating function. The gen-set nominal power is decreased according to
the adjusted curve.
The setpoint actual physical dimension is given by the related analog input and the value assigned to it.
Step:
1 X
Range:
± 32000 X
Force value possibility: Yes
Hint:
DeratingX strt
unit [X] depends on DeratingPowerX analog input unit. It can be e.g.°C in case of temperature
derating function.
Derating1 end
[ X ] (FV)
Derating2 end
[ X ] (FV)
Ending value for power limitation – at this value the gen-set power is limited to
DeratingX pwr
value and it
won’t go lower for higher input values.
The setpoint actual physical dimension is given by the related analog input and the value assigned to it.
Step:
1 X
Range:
± 32000 X
Force value possibility: Yes
Hint:
To record the power derating activity into the History:
- Configure the binary output Derating X act to a virtual periphery input.
- Configure either “History record” or “Warning”-protection type to this input to record power derating
activity in History and optionally to indicate it in Alarmlist.