Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
28
Hint:
The sensor fail alarm does not influence the gen-set operation
Blocking types
B
LOCKING TYPE
D
ESCRIPTION
All the time
The alarms are beeing evaluated all the time the controller is switched on.
RunOnlyBlkDel1
The alarms are beeing evaluated only while the gen-set is running. The evaluation
begins
RunOnlyBlkDel1
seconds after the engine has been started.
RunOnlyBlkDel2
The alarms are beeing evaluated only while the gen-set is running. The evaluation
begins
RunOnlyBlkDel2
seconds after the engine has been started.
RunOnlyBlkDel3
The alarms are beeing evaluated only while the gen-set is running. The evaluation
begins
RunOnlyBlkDel3
seconds after the engine has been started.
Force block 1
The alarms are beeing evaluated while the input
Force block 1
is not active. The
evaluation begins
ForceBlockDel1
seconds after the input has been deactivated.
Force block 2
The alarms are beeing evaluated while the input
Force block 2
is not active. The
evaluation begins
ForceBlockDel2
seconds after the input has been deactivated.
Force block 3
The alarms are beeing evaluated while the input
Force block 3
is not active. The
evaluation begins
ForceBlockDel3
seconds after the input has been deactivated.
El. prot
The alarms are beeing evaluated while the generator is expected to provide correct
voltage and frequency. That means the alarms start to be evaluated after transition
form
Idle
to
Running
phase when the period of
Max stab time
has already elapsed,
remain beeing evaluated while the gen-set is running at nominal speed (regardless
of GCB position) and stop to be evaluated by transition to the
Cooling
phase.