Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
26
Alarm types
A
LARM
/E
VENT
KIND
L
EVEL
D
ESCRIPTION
Warning 1
The alarm appears in the Alarmlist and is recorded into the history log.
Activates the output Common Wrn as well as the standard alarm outputs.
Alarm Only
1
The alarm appears only in the Alarmlist.
Activates the output Common Al as well as the standard alarm outputs.
HistRecOnly 1
The event is recorded into the history.
Activates the output Common Hst for one second. Standard alarm outputs
are not activated.
AL indication
1
The event is only indicated in the Alarmlist.
It disappear for the alarmist automatically as soon as the cause
disappears.
Standard alarm outputs are not activated.
A+H indication
1
The event is only indicated in the Alarmlist and recorded into the history
log.
It disappear for the alarmist automatically as soon as the cause
disappears.
Standard alarm outputs are not activated.
Shutdown 2
The alarm appears in the Alarmlist and is recorded into the history log.
It causes immediate stop of the gen-set without unloading and cooling
phase.
The gen-set can't be started again while there is a Shutdown alarm in the
Alarmlist.
Activates the output Common Sd as well as the standard alarm outputs.
Slow Stop
2
The alarm appears in the Alarmlist and is recorded into the history log.
It causes stop of the gen-set by the standard stop sequence, i.e. including
unloading and cooling phase.
The gen-set can't be started again while there is a Slow stop alarm in the
Alarmlist.
Activates the output Common Stp as well as the standard alarm outputs.
Off Load
2
The event appears in the Alarmlist and is recorded into the history log. It
does not require confirmation, diappears by itself.
It causes immediate opening of the GCB. In AUT and SEM modes the gen-
set remains running for 60 seconds and then it is stopped by the standard
stop sequence. In MAN mode the gen-set remains running until the
operator changes it's operational state manually.
If the controller is in AUT or SEM mode and all previously active Off load
alarms disappeared the gen-set is automatically started back and
connected to the load if the condition for the gen-set to be running persists
(e.g. Rem start/stop is active ..).
This event is used to put the gen-set temporarily off the load for any
reason.
Activates the output Common OfL.