Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
67
#SysBaseLoad
[ kW – MW* ]
From this value, the requested gen-set group power is calculated, according to the number of gen-sets
running. The complete system produces the power equal to this value. Active only when
SysLdCtrl PtM
=
BASELOAD.
Step:
0,1 kW / 1 kW / 0,01 MW*
Range:
0,1 kW – 650,00 MW*
*Note:
The actual setpoint units and range depend on setting of the Power format (see GenConfig manual).
Hint:
If you set this setpoint to a higher value than the system is available to produce, the total produced power is
limited with the sum of Nomin power setpoints of all gen-sets in the system.
LocalBaseload
[ kW – MW* ]
(FV)
If the value is OFF, the gen-set takes part in the
#SysBaseload
production or in Load Sharing. If it is set to a
certain value, the gen-set produces this power regardless of the other gen-sets. It is taken out from the PMS
in this case.
If the gen-sets operate in island parallel mode, the requested
LocalBaseload
value can be reduced if the
actual load is lower than this value. The gen-sets in the group will try to match their
LocalBaseload
s based
on their addresses, so the first limited would be the one with the highest CAN address.
Step:
0,1 kW / 1 kW / 0,01 MW*
Range:
OFF, 0,1 kW -
Nomin power*
Force value possibility: Yes
*Note:
The actual setpoint units and range depend on setting of the Power format (see GenConfig manual).
Hint:
In the case the total load of the gen-set group which work in LocalBaseload mode is dropping and the load of
the gen-set of the highest address is under 5% of its nominal power then the gen-sets of the second and first
highest address get to load sharing mode together (see the picture below).
Ac
tu
al load
[ kW ]
Time
5
%
o
f Runn
in
g
nom
. p
owe
r
Ge
n
1
Ad
d. 1
Ge
n2
Add
. 2
G
en3
Add.
3
Actual powe
r [ kW
]
Time
LocalBaseload = OFF
LocalBaseload = 100% Nom. Power
LocalBaseload = 100% Nom. Power