Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
57
Common BOC
The output closes if any “Breaker Open & Cool-down”-protection type appears. The output opens, if no
“Breaker Open & Cool-down”-protection type is active and FAULT RESET has been pressed.
Common Stp
The output closes if any “Slow stop”-protection type appears. The output opens, if no “Slow stop”-protection
type is active and FAULT RESET has been pressed.
Common Sd
The output closes if any “Shutdown”-protection type appears. The output opens, if no “Shutdown”-protection
type is active and FAULT RESET has been pressed.
Common SdOvr
Common output that gets active with 2s delay if any Shutdown override-type protection becomes active. If it
is already active and another protection of that type becomes active, the output is deactivated for 2 seconds
and then reactivated again to inform on this new alarm.
CommonActLev 2
The output is a logical OR of Common BOC, Common Stp and Common Sd outputs.
CommonAlLev 2
The output is active if at least one of the 2
nd
level alarms (BOC, Stp, Sd) is active or not yet confirmed.
Common Fls
The output closes if any “Fail sensor”-protection type appears. The output opens, if no “Fail sensor”-
protection type is active and FAULT RESET has been pressed.
T cyl differ
Output closes when engine cylinder temperature difference warning is active.
Vgen <>
The output closes if the generator over/under voltage protection becomes active. Alarm appears in the alarm
list as an effect of this protection.
Vbus <>
The output closes if the bus over/under voltage is detected.
Overcurrent
The output closes if the generator IDMT Overcurrent or Shortcurrent alarm activates. The output opens, if
none of these alarms is active and FAULT RESET has been pressed.