Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
34
CB open command:
BO: CB close/open
Transition closing -> opening (opening command is issued during closing pulse):
2s
BO: CB OFF coil
BI: CB fdb neg
BI: CB fdb
BO: CB UV coil
Further behavior of UV output
depends on the system status. In
case of transition to cooling stays
off, if the Cb was opened manually
and the engine keeps running, it
activates again after timeout
elapses.
During CB opening the CB status
LBO is deactivated with change of
the first feddback status
BO: CB status
BO: CB close/open
<2s
2s
BO: CB OFF coil
BI: CB fdb neg
BI: CB fdb
BO: CB UV coil
BO: CB status
BO: CB ON coil
Closing pulse is shortened, opening
sequence is started immediatelly
CB opening by protection or manual
command (button pressed)