Force value possibility: Yes
Off load
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when an Off load type
protection occurs.
Force value possibility: Yes
Hint:
If enabled for an SMS type active call, an empty Alarmlist is sent, as this type of protection does not appear
there.
BrkOpen&CoolDn
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a
BrkOpen&CoolDn type protection occurs.
Force value possibility: Yes
Mains protect
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Mains protect
type protection occurs.
Force value possibility: Yes
Hint:
If enabled for an SMS type active call, an empty Alarmlist is sent, as this type of protection does not appear
there.
Slow stop
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Slow stop type
protection occurs.
Force value possibility: Yes
Shutdown
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Shutdown type
protection occurs.
Force value possibility: Yes
AcallCH1..3-Type (FV)
Up to three separate channels are available for any of the following types of messages:
DISABLED:
Channel is disabled.
DATA-ANA:
Standard analog modem connection to monitoring SW.
DATA-GSM:
Standard GSM modem connection to monitoring SW.
DATA-ISDN:
Standard ISDN modem connection to monitoring SW.
DATA-CDMA:
CDMA modem connection to monitoring SW.
SMS-GSM:
Channel sends SMS message via GSM network. Only with GSM modem connected.
SMS-CDMA:
Channel sends SMS message via CDMA network. Only with CDMA modem connected.
IB-E-MAIL: Channel
sends
E-mail. Only when IG-IB connected.
IB-EML-SMS:
Channel sends E-mail in short format (SMS). Only when IG-IB connected.
Force value possibility: Yes
An Email contains
-
header with serial number and application info
-
Alarm list contents
-
latest 20 History records (reason, date, time)
Example of EML-SMS:
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
Hint:
GSM modem must be connected to controller for Active GSM call or SMS.
IG-IB does not support direct SMS, just as an email.
Connected device type (Analog / GSM / ISDN / CDMA modem) is recognized automatically.