IssueActCallC1
IssueActCallC2
IssueActCallC3
Rising edge on these binary inputs forces an active call to be issued via the corresponding channel.
Hint:
Can be used to send e.g. SMS in the case of a mains failure to report that the engine has successfully
started (linked from the output Gen params OK) and later on to report that the engine has stopped again
(linked from the inverted output Fuel solenoid).
ECUComFailBlck
The input blocks the issuing of the alarm in case of ECU communication failure.
Startblocking
The input blocks the engine start. If active, NotReady state is shown on the controller screen and a message
appears in the Alarmlist. As soon as input is deactivated, engine start is enabled again.
Hint:
Use this input for cooperation with external supervisory device, such as PLC. It can prevent the engine to be
started because of some reasons not known to the controller.
ECU StoppedEng
Engine stop was activated in ECU, not from controller. The controller reflects this situation and also goes to
Stop to avoid an Underspeed alarm (and record in the Alarm list).
CtrlHBeat sens
This input is used at a redundant controller to sense the "heart beat" from the main controller. The input is to
be connected to the output CtrlHeartBeat of the main controller.
If the redundant controller does not sense the heart beat from the main one, it will activate the binary output
CtrlHBeat FD, which has to be wired such a way, that it disconnects the dead main controller from the
genset, connects the redundant controller instead and activates it.
Force value 1 …16
If any of the particular 16 input s is active, the Force value function on that corresponding channel gets
active, forcing an alternative value to the selected setpoint.
CylDifEvalBlk
If the signal is active, the protection based on the difference amongst cylinder temperatures is blocked. After
signal deactivation, the protection is unblocked immediately.
CylDifEvalDel
Internal prot activity
CylDif evaluates deviation
BI: CylDifEvalBlk
CylDif Prot active