Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
12
Hint:
Optional functions in absolute or relative Power management are:
- Running hours balancing (equalization),
- Load demand (different size) engines swap and
- Power management of two or more gen-set groups (bus tie support).
Running hours balancing
The gen-sets priorities are automatically swapped to balance engine running hours. Up to 32 controllers are
supported.
Activation: #
PriorAutoSwap
= RUN HOURS EQU
Important setpoints:
RunHoursBase
,
#RunHrsMaxDiff
Different sized engines (Load demand) swap
Three running engines (priorities) are swapped based on load demand (one “small” engine runs on “small”
load and swaps to another one “big” engine that runs when load increases).
Activation: #
PriorAutoSwap
= LD DEMAND SWAP
Important setpoints:
#PwrBandContr1
,
#PwrBandContr2
,
#PwrBandContr3, #PwrBandContr4
,
#PwrBandChngDe
.