Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
88
CylDifEvalDel
[ s ]
Cylinder temperature Difference Evaluation Delay.
Step:
1s
Range:
0 – 600 s
Cylinder temperature deviation protection type: warning
Gen-set power
C
y
linde
r t
e
m
per
at
ur
e
d
e
vi
at
io
n
fr
om
a
v
er
a
ge
M ax+CylDifPm in
M ax-CylDifPm in
M ax+CylDifPnom
Nom inal power
Pm inCylDifEval
M ax-C ylDifPnom
+
-
Average temperature
Drawing text translation
Cylinder temperature deviation from average
Cylinder temperature deviation from average
Average temperature
Average temperature
Max+CylDifPmin
Max+CylDifPmin
Max-CylDifPmin
Max-CylDifPmin
PminCylDifEval
PminCylDifEval
Max+CylDifPnom
Max+CylDifPnom
Max-CylDifPnom
Max-CylDifPnom
Nominal power
Nominal power
Gen-set power
Gen-set power
Service time 1
[ h ]
Service time 2
[ h ]
Service time 3
[ h ]
Service time 4
[ h ]
Running hours down counters are decremented when engine is running. Service alarm is indicated in Alarm
list and History record is activated when at least one of the counters reaches zero.
Service time X
setpoints
are actual counter values.
Step:
1 h
Range:
0 – 65534 h; OFF
Hint:
Once a service time has elapsed the corresponding
Service time X
setpoint must be adjusted again to a non-
zero value to clear the alarm and begin a new countdown.
You can rename the particular timers using Translator in GenConfig to indicate specific service intervals –
e.g. “OilChange time”, “SparkPlug time”, ...
Service Time
can be switched off if
Service Time X
= 65535 (OFF).
Analog protect
The content depends on programmable protections settings. This list contains pre-set protections from
default archives: