Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
59
Batt volt
Indication of battery voltage protection based on
Analog protection
:
Batt >V
,
Batt <V
,
Batt V del
.
EarthFaultCurr
Indication of Earth fault current protection based on
Gener protect
:
EarthFaultCurr
and
EthFltCurr del
.
Dongle incomp
Incompatible (usually missing) dongle indication.
Hint:
The incompatible dongle is indicated e.g. in the case that:
- power management is enabled (
Pwr management
:
Pwr management
<> DISABLED) and there is no
dongle detected that enables this feature
- load sharing function is enabled (
Process control
:
#SysLdCtrl PtM
= LDSHARING or (
Process control
:
#SysLdCtrl PtM
= BASE LOAD and logical binary output MCB STATUS = 0 at the same time and controller
is not alone on the CAN bus)) and there is no dongle detected that enables this feature.
Incompatible dongle is not indicated in case of MINT operated in single island operation (no other controllers
detected on the CAN bus).
Emergency stop
Activity of Emergency stop (from Binary input Emergency stop) indication.
Hint:
Any Binary output alarm indication that follows the corresponding internal state is activated with alarm and
stays active until alarm reason disappears and the Fault reset (panel button or remote) is activated.
WrnSe2
The output closes when ServiceTime1 or ServiceTime2 has reached zero. To reset the output (and the
related WrnSeT2), it is necessary to set again a non-zero value to the corresponding setpoint.
WrnSe4
The output closes when ServiceTime3 or ServiceTime4 has reached zero. To reset the output (and the
related WrnSeT4), it is necessary to set again a non-zero value to the corresponding setpoint.
Overspeed
The output closes if the gen-set over speed alarm activates. The output opens, if alarm is no more active and
FAULT RESET has been pressed.
Underspeed
The output closes if the gen-set under speed alarm activates. Under speed limit is given by
Starting RPM
if
the engine has already started (see Starting procedure description). The output opens, if alarm is no more
active and FAULT RESET has been pressed.
Start fail
The output closes if the gen-set start-up fails (= Cranking issued
Crank attempts
times and engine did not
start). The output opens, if alarm is not active and FAULT RESET has been pressed.
Sd Stop fail
Engine stop fail indication. Stop fail: engine does not reach “still engine” condition within
Engine params
:
Stop time.
ChrgAlternFail
Charger fail detection. Guaranteed level for signal Charging OK = 80% of supply voltage.
Hint:
D+ output current is limited to cca 300 mA.