Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
39
Inputs and Outputs
Virtual and physical modules
Number of I/O can be extended and project wiring can be reduced using the following extension and virtual
modules.
Module name
BIN
BOUT
AIN
AOUT
Note
IGS-NT controller
x
x
x
x
Number of I/O depends on type.
IGS-PTM
8
8
4
1
Standard I/O extension module.
IS-AIN8
-
-
8
-
Standard I/O extension module.
IS-BIN16/8
16
8
-
-
Standard I/O extension module.
I-CB
x x x x Configurable
communication
bridge.
IGL-RA15
-
15
-
-
15 Green, Red, Yellow LED panel.
I-AOUT8
-
-
-
8
8 Analog outputs
VPIO
8
8
-
-
Virtual periphery I/O module.
SHBIN
8
-
-
-
SHared (virtual) Binary INput module
SHBOUT
-
8
-
-
SHared (virtual) Binary OUTput module
SHAIN
-
-
8
-
Shared (virtual) Analog INput module
SHAOUT
-
-
-
8
Shared (virtual) Analog OUTput module
PLC
x
x
x
x
Programmable (internal) logic module.
Hint:
For more details about Virtual peripherals (Shared and Internal virtual I/O periphery and PLC) see IGS-NT-
Application guide-2.2.pdf.
Binary Inputs - Control
Sys start/stop
If the input closes, the controller may start the engine (in AUT mode only). Request to start depends on state
of setpoint
Pwr management:
Pwr management
state and, if ENABLED, on the actual need of load reserve.
I.e. all controllers in the system should have their Sys start/stop inputs active, but it doesn’t mean that all
engines are running.
If
Pwr management:
Pwr management
is DISABLED, the closed input requests the engine to start
regardless of the load reserves.
Gen-set is running both in mains parallel or island parallel (depends on mains condition). Reaction on input
state change is delayed by setpoints
#SysAMFStrtDel
/
#SysAMFStopDel
in island mode, by 1 sec in mains
parallel mode (= input MCB feedback active).
Hint:
It is necessary to provide valid Sys start/stop input to the all interconnected units otherwise their will not start
automaticaly. Use wire or virtual periphery SHBOUT/SHBIN.
Emergency stop
If the input is activated, engine shutdown is immediately issued. It has a character of a “Shutdown” -
protection type, however some special behaviour follows in the case of its activation:
-
Outputs Ignition, Ventilation, Cooling pump, Prelubr pump are switched off, regardless of the engine
state.
-
This input cannot be overridden with the input Sd override.
Hint:
Alarm type is set to “No protection”, as this input itself creates the shutdown protection.