Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
61
running.
This output also influences evaluation of communication failure with ECU and related FLS alarms from
analog inputs read from the ECU. If the output is configured (which means configured on physical binary
output or VPIO output), the issuing of communication error is blocked during Prestart and Stopping
procedure as shown in the picture.
Hint:
The input must be configured on physical binary output or VPIO output. It is not enough to configure it as a
PLC input for example.
Generator Voltage and Frequency alarms indication
Basic settings
:
FixVoltProtSel
= PHASE-NEUTRAL
Binary output name
Protection type
Based on setpoint
BOC L1 under
BOC L2 under
BOC L3 under
BreakerOpen & Cool-down
Gener protect:
Gen <V BOC, Gen V del
BOC L1 over
BOC L2 over
BOC L3 over
BreakerOpen & Cool-down
Gener protect:
Gen >V BOC, Gen V del
Sd L1 over
Sd L2 over
Sd L3 over
Shut-down
Gener protect:
Gen >V SD
Gener protect:
Gen V del
Gen V L1-N
Gen V L2-N
Gen V L3-N
BreakerOpen & Cool-down
Shut-down
Gener protect:
Gen <V BOC
Gener protect:
Gen >V BOC
Gener protect:
Gen >V SD
Gener protect:
Gen V del
Basic settings
:
FixVoltProtSel
= PHASE-PHASE
Binary output name
Protection type
Based on setpoint
BOC L12 under
BOC L23 under
BOC L31 under
BreakerOpen & Cool-down
Gener protect:
Gen <V BOC
Gener protect:
Gen V del
BOC L12 over
BOC L23 over
BOC L31 over
BreakerOpen & Cool-down
Gener protect:
Gen >V BOC
Gener protect:
Gen V del
Sd L12 over
Sd L23 over
Sd L31 over
Shut-down
Gener protect:
Gen >V SD
Gener protect:
Gen V del
Beginning of
Prestart
Fuel
solenoid
deactivation
ECU
communication
failure alarm
blocked
End of
Prestart
Engine
stopped
t