Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
85
ResetActAlarms
[ DISABLED / ENABLED ]
DISABLED:
If Fault reset is activated (from any source), only inactive (normally displayed) alarms are
reset. So only inactive alarms can be cleared from the Alarmlist.
ENABLED:
If Fault reset is activated (from any source), all currently present (including inverse displayed
= active) alarms are reset (asterisk in Alarmlist disappears for all present alarms). I.e. after an active (inverse
displayed) alarm later on becomes inactive (normally displayed), it is cleared automatically from the Alarmlist
if previously reset.
Hint:
ENABLED mode corresponds to the way that IG and IS controllers (previous generation) handled the
alarms.
RunOnlyBlkDel1
[ s ]
Delay for Engine running Alarms activation – group 1 – see drawing below.
Step:
0,1s
Range:
0,0 – 3000,0 s
RunOnlyBlkDel2
[ s ]
Delay for Engine running Alarms activation – group 2.
Step:
0,1s
Range:
0,0 – 3000,0 s
RunOnlyBlkDel3
[ s ] (FV)
Delay for Engine running Alarms activation – group 3.
Step:
0,1s
Range:
0,0 – 3000,0 s
Force value possibility: Yes
BINARY INPUT
BinInp delayX
physical
closed
Engine running
state
RunOnlyBlkDel
PROTECTION
active
inactive
Hint:
Engine running state =
RPM >
Engine params
:
Starting RPM
or
Analog input Oil pressure >
Engine params
:
Starting POil
or
D+ terminal active and
Engine params:
D+ function = ENABLED or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3 or
Vgen > 15 V (any phase).