Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
54
Aut mode
The output is closed, if AUT mode is selected.
Gen params OK
The output is copy of generator status LED on controller front panel. The output is closed if gen-set is
running and all generator electric values are in limits and no 2
nd
level alarm is active (when only 1
st
level
alarm is active, the output is closed).
Hint:
Use this output for switching on of auxiliary device (e.g. cooling pump) driven from generator voltage
independently on the GCB status.
Bus params OK
The output is copy of bus status LED on controller front panel. The output is closed if bus electric values are
in limits.
In synchronism
The output closes during synchronizing if all matching conditions are fulfilled. It opens if corresponding
breaker is closed (xCB status output get active).
Hint:
Synchronizing matching conditions:
- Slip frequency < 0,25 Hz
- Gen to Mains/Bus voltage phase shift within
Sync/Load ctrl:Phase window
- Gen and Mains/Bus voltages within
Sync/Load ctrl:Voltage window
- Sync/Load ctrl:Dwell time
elapsed
StartButnEcho
StopButnEcho
FltResButnEcho
HrnResButnEcho
GCBButnEcho
These outputs are active for 1s if the corresponding button is pressed or binary input gets active or remote
command is issued (from PC software, SMS, ...).
Hint:
This function is valid only when command is allowed. (Pulse is not generated in OFF mode and during start
procedure).
All functions related to front panel buttons depends on setpoint settings
Basic settings
->
Local Button
CtrlHeartBeat
The output signalizes watchdog reset. In a healthy state it flashes at 500ms : 500ms rate. It stops flashing
when the unit reset occurs and the new controller start-up fails.
Bin selector 1-4
The outputs are active according to the corresponding setpoints
Engine params:
Bin selector X
. These are
used for particular ECU settings.
Logical 0
Constant value that can be configured to any output.
Logical 1
Constant value that can be configured to any output.