Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
52
RemoteControl1
RemoteControl2
RemoteControl3
RemoteControl4
RemoteControl5
RemoteControl6
RemoteControl7
RemoteControl8
These outputs are controlled remotely from InteliMonitor or other tool. The user selects the requested state
of these outputs via the buttons in this program.
Hint:
Outputs can be used to switch on/off some auxiliary devices in the control panel.
Binary outputs – Status information
Ready for load
The output closes when the engine is running, no 2
nd
level protection is active and the GCB is already closed
or is able to be closed (i.e. all generator parameters are within limits).
Gen-set active
The output closes together with Prestart output and opens together with achieving “still engine” condition
after the stop command. If the start sequence finishes with Start fail, the output opens after the last
unsuccessful start attempt.
Hint:
The output also closes if the engine begins to rotate spontaneously. It stays closed until “still engine”
condition is achieved.
Operational
The output is closed when no protection is active and the gen-set is ready for operation or is currently in
operation.
Ready
The output is closed, if following conditions are fulfilled:
- Gen-set is not running and
- No 2
nd
level protection is active (or not yet reset)
- The controller has no “engine running” indication from any source
- The controller is not in OFF mode
Not ready
The output is closed, if following conditions are fulfilled:
- The controller in OFF mode or
- Any 2
nd
level alarm is active or not yet reset
CrankProcedure
The output closes together with the first Starter activation and opens with the last Starter deactivation (either
“engine running” state achieved, or Start fail). During crank pauses, the output stays closed.