Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
42
Force block 1
Force block 2
Force block 3
Three binary inputs for user-specific blocking of programmable protections. If the particular input is active, all
the protections with the corresponding “Force block X” block type are blocked.
Load res 2
Load res 3
Load res 4
If the input LOAD RES X is closed, the setpoint set
Pwr management:
#
LoadResStrt X
+
#LoadResStop X
(
#%LdResStrt X
+
#%LdResStop X
)
will be selected. Higher index has higher priority when more these
binary inputs are closed together. When not configured or not active, setpoint set
#
LoadResStrt 1
+
#LoadResStop 1
(
#%LdResStrt 1
+
#%LdResStop 1
)
is used.
Hint:
All controllers operating in Power management must have the same Load reserves selected.
It is possible to use Virtual periphery to share the signals between more controllers on the CAN bus. In such
case one controller is a server which physically has the signals connected and other controllers get these
signals via CAN bus.
Setpoint set selection depends on the
#Pwr mgmt mode
– if set to ABS (kW or kVA),
#LoadResStrt X
type
setpoints are active, if set to REL (%),
#%LdResStrt X
type setpoints are active.
MinRun power 1
MinRun power 2
MinRun power 3
When binary input MinRun power 1 or 2 or 3 is closed, the corresponding setpoint
Pwr management:
#MinRun power 1
or
2
or
3
is selected. Higher index has higher priority when more these binary inputs are
closed together. When not configured or not active, minimal running power is 0, i.e. the system works only
based on Load reserves.
Hint:
All controllers operating in Power management must have selected the same MinRun power input.
It is possible to use Virtual periphery to share the signals between more controllers on the CAN bus. In this
case one controller is a server which physically has the signals connected and other controllers get these
signals via CAN bus.
Priority sw A (Priority switch A)
Priority sw B (Priority switch B)
Priority sw C (Priority switch C)
Priority sw D (Priority switch D)
Binary inputs for priority selection.
Priority value Priority 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Priority sw A
0 or nc
1 0 1 0 1 0 1 0 1 0
1
0
1
0
1
Priority sw B
0 or nc
0 1 1 0 0 1 1 0 0 1
1
0
0
1
1
Priority sw C
0 or nc
0 0 0 1 1 1 1 0 0 0
0
1
1
1
1
Priority sw D
0 or nc
0 0 0 0 0 0 0 1 1 1
1
1
1
1
1
Hint:
Priority value is defined by setpoint Priority when all Priority switches are opened or not configured.