Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
92
2,0
No action
200
100
40
20
10
4
2
5,0
No action
500
250
100
50
25
10
5
10,0
No action No action
500
200
100
50
20
10
20,0
No action No action No action
400
200
100
40
20
50,0
No action No action No action No action
500
250
100
50
!!! VERY IMPORTANT !!!
•
The maximum input range of the controller current terminals is 11 Amps. Anything over this
value is displayed as measured limit, e.g. 15 Amps from CT is measured and displayed as 11
Amps.
•
Take special care when selecting CT’s. All available 5 Amp CT’s do not have a range up to 11
Amps.
Igen
Nominal current
Ishort
2Inom del
Maximal Reaction time
R
e
act
io
n
ti
m
e
Gen >V BOC
[ % ] (FV)
Threshold for generator over voltage in % of nominal voltage.
Step:
1 %
Range:
Gen <V BOC
– 150 % of
GenNomV
or
GenNomVph-ph
respectively
Protection:
BreakerOpen & Cool-down.
Gen <V BOC
[ % ] (FV)
Threshold for generator under voltage in % of nominal voltage.
Step:
1 %
Range:
50 –
Gen >V BOC
% of
GenNomV
or
GenNomVph-ph
respectively
Protection:
BreakerOpen & Cool-down.
Hint:
All three phases are checked for generator voltage protection. Minimum or maximum out of three is used.
Gen >V Sd
[ % ] (FV)
2
nd
threshold for generator over voltage in % of nominal voltage.
Step:
1 %
Range:
50 – 150 % of
GenNomV
or
GenNomVph-ph
respectively
Protection: Shutdown.