Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
110
PLC settings
The content depends on actual PLC configuration. Contains all setpoints related to the configurable PLC
blocks. If this setpoint group is empty, it is not displayed.
Timer channel 1-16
Defines the setting of particular timer channel.
There is 16 channels, each defines occurrence date and time (year, month, day, hour, minute), duration time
(in minutes, maximum is 24*60), repeating period (day, week, month, once). In case of week – day of the
week selection, when should be ex selection of repeating (every 1
st
, 2
nd
, 3
rd
or 4
th
week); In case of
month – day of the month selection (e.g. every 3
rd
day or every 2
nd
Monday)
Every channel can be disabled by blocking input. If blocking input is active then the timer is not activated
even if it should be, according to it’s other settings.
The channels are divided into groups of 4. Each group has independent binary output, which activates if any
of the 4 channels within the group is active (1-4, 5-8,...), see the picture below. There is also one common
output for all 16 channels.
Hint:
Timer channel 1-16 can be set via Pc software only. See Reference guide for GenConfig.
Act. calls/SMS
History record
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a History record
type “protection” occurs.
Force value possibility: Yes
Hint:
If enabled for an SMS type active call, an empty Alarmlist is sent, as this type of protection does not appear
there.
Alarm only
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when an Alarm only
type protection occurs.
Force value possibility: Yes
Warning
[ DISABLED / ENABLED ]
(FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Warning type
protection occurs.