Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
47
Language
index
-> given
by
display
setting
1 2 3 4 5 6 7
Lang
sel
int
A
0
1 0 1 0 1 0 1
Lang
sel
int
B
0
0 1 1 0 0 1 1
Lang
sel
int
C
0
0 0 0 1 1 1 1
Hint:
Warning – each language change causes the restart of the respective display (not the whole controller), so
the display’s control panel won’t react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.
Lang sel D#2 A
Lang sel D#2 B
Lang sel D#2 C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the controller’s external
terminal with address #2 – for IG-based controllers the IG-Display, for IS-based controllers the IS-Display
with address #2.
Encoding of binary inputs’ combinations:
Language
index
-> given
by
display
setting
1 2 3 4 5 6 7
Lang
sel
D#2
A
0
1 0 1 0 1 0 1
Lang
sel
D#2
B
0
0 1 1 0 0 1 1
Lang
sel
D#2
C
0
0 0 0 1 1 1 1
Hint:
Warning – each language change causes the restart of the respective display (not the whole controller), so
the display’s control panel won’t react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.
Lang sel D#3 A
Lang sel D#3 B
Lang sel D#3 C
Set of binary inputs for forcing alternative languages. This set of inputs is switching the IS-Display with
address #3.
Encoding of binary inputs’ combinations:
Language index ->
given by display setting
1
2
3
4
5
6
7
Lang sel D#3 A
0
1
0
1
0
1
0
1
Lang sel D#3 B
0
0
1
1
0
0
1
1
Lang sel D#3 C
0
0
0
0
1
1
1
1
Hint:
Warning – each language change causes the restart of the respective display (not the whole controller), so
the display’s control panel won’t react until the restart has finished (~ 5s).
Value 0 in the table denotes that the corresponding input is not active or not configured.
If more than 7 languages are present in the controller, it is not possible to force languages with index higher
than 7 using these binary inputs.
The reaction on BI combination change is 1s delayed not to react on transient combinations if a rotary
selector switch is used.