ECU comm error
Output closes if there is an error in the communication with ECU. It doesn’t matter how the ECU is
connected – J1939 link or RS232 line.
PeriphCommErr
Output closes if there is an error in the communication with any peripheral unit (e.g. IS-AIN8, IGS-PTM, ...).
CtrlHBeat FD
This output is used at a redundant controller to disconnect the main controller from the gen-set, connect the
redundant one instead and activate it. The output is closed:
- If the input CtrlHBeat sens is configured onto any input terminal and the redundancy controller does not
sense the "heart beat" signal from the main controller at that terminal.
- If the redundant controller has not received two consequent messages from the main controller. The
address of the main controller for the particular redundant one is selected by the the setpoint Watched Contr
CAN2 bus empty
The output closes if the controller doesn’t “see” any other controllers on the CAN2 bus. The output activation
can be blocked by setpoint
Basic settings
:CAN2empt
Detect
(So it should be DISABLED for single
applications.)
Bus meas error
The output closes when bus measurement protection is activated according to description of
Gener
protect
:
BusMeasError
setpoint.
Binary outputs – Configurable prog. States
J1939
Indication of J1939 communication fail (configurable between Nop protection, Warning or Shutdown).
KWP2000
Indication of KWP2000 communication fail.
SHBinCfGErr
Shared Binary module configuration error – i.e. more than one source was configured (is on the CAN2 bus).
SHAinCfgErr
Shared Analog module configuration error – i.e. more than one source was configured (is on the CAN2 bus).
PLC State 1 .. 4
PLC state indication.
ECUDiagBlocked
Output is active if any ECU is configured and when
Basic setting
:
ECU diag
= DISABLED.
Hint:
No ECU alarms are displayed on the controller screen.
WrongConfig
Wrong controller configuration indication.
Reverse power
Output is active when reverse power protection is active. Based on
Gener protect
:
Reverse power
and
RevPower del.