LCD brightness
Analog input for external LCD brightness setting (e.g. via potentiometer). Keyboard LCD brightness setting
and binary input Alt brightness do not work when input is configured. Expected value is in the range 0 to
100%.
Hint:
In IG-NT/EE and modifications, this input controls the backlight of the built-in display. For optionally attached
IG-Display module, this input has no meaning.
In IS-NT and modifications, this input controls the backlight of the IS-Display with address #1. For optional
displays with addresses #2 and #3, this input has no meaning.
Cold Temp 1-4
In case there is a separate thermocouple sensor for measuring the “cold end” of cylinder temperatures
evaluation, configure that sensor to this analogue function.
Analog outputs
The IS-NT has one analog output available. Default setting of this output is the value of actual generator
power in the range 0 to 20 mA.
Hint:
It is possible to configure any other value available in the configuration using GenConfig.
If the output range 4 to 20 mA is needed, the limits for analog output should be set according to an example
in the following table:
Requested power range
Controller analog output setting
0 – 1000 kW
Low limit: -250 kW
High limit: 1000 kW
Low
–
High
kW
Low limit:
Low
- (
High
–
Low
)/4 kW
High limit:
High
kW
This setting ensures that 0 kW (Low kW) will correspond to 4 mA.
Values
Value Description
Dimension
InteliMonitor
IG-NT
IS-NT
Engine values
RPM Rotation
per
minutes RPM
YES
YES
YES
Sync/Load ctrl group
ActPwrReq Actual
power
request kW
YES
NO
NO
SpeedReqOut
Speed request output
V
YES
YES
YES
Speed request
Speed request
%
YES
NO
NO
SpeedReq RPM
Speed request RPM
RPM
YES
NO
NO
ReqEngineSpeed Requested
engine
speed*
RPM
YES
NO
NO
SystLoadCtrl System
load
control
-
Yes NO
NO
TotRunPact Q
Total run power aktive Q
kVAr
YES
NO
NO
TotRunPact P
Total run power aktive P
kW
YES
YES
YES
netPgnemPh
Sum of all P gen-sets
synchronized on bus
kW YEs
NO
NO
Volt/PF ctrl group
VoltRegOut
Voltage regulator output
%
YES
YES
YES