Inteli NT MINT, SW Version 2.6, ©ComAp – November 2011
IGS-NT-MINT-2.6-Reference Guide.PDF
14
If manual reconnection of the load is desired, the AutoLd recon setpoint needs to be disabled (
AutoLd recon
=
DISABLED) and the MAN load recon binary input needs to be configured.
Rising edge on this input resets the controller to a lower stage, but only if the load is under the
Ld recon level
at that moment.
Hint:
If no Load Shedding outputs are configured, there is no record to history and no scrren timer indication of the
activity of this function.
Load reconnection – automatic ->
AutoLd recon =
ENABLED
Ld recon del
Ld recon del
Ld recon del
BO Load shed 2
Ld recon level
Gen-set power
BO Load shed 3
BO Load shed 1
opened
opened
opened
Load reconnection – manual ->
AutoLd recon =
DISABLED