3. Choose the contact directions of the BL1 IN and BL2 IN multifunc
tion inputs by setting the AP098 and AP099 parameters.
Tab.66
Parameter
Description
AP098
Blocking input 1 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
AP099
Blocking input 2 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
4. Configure the temperature offsets for the voluntary overheating by
configuring the HP091 and HP092 parameters.
Tab.67
Parameter
Description
HP091
Offset temperature of heating setpoint when
photovoltaic function is activated
HP092
Offset temperature of DHW setpoint when
photovoltaic function is activated
10.5.12 Reducing the noise level of the outdoor unit
Silent mode is used to reduce the noise level on the outdoor unit during a
given time range, particularly at night. This mode gives temporary prece
dence to silent running rather than temperature control.
Important
Silent mode only operates if the silent running kit is connected
to the outdoor unit.
This package is not compatible with the AWHP 4.5 MR outdoor
unit.
Silent mode is managed by the following parameters which can be found
in the Installer menu, EHC–04, ADV:
Tab.68
Parameter
Description
HP058
Enabling Heat pump Silent mode
HP094
Start time of the low noise when option activated
HP095
Stop time of the low noise when option activated
10.5.13 Detecting an additional or replacement PCB
The automatic detection function is used if a control PCB has been re
moved, replaced or added.
1. Go to the Installer menu.
2. Access the Installer menu by entering the code 0012 by pressing the
and keys.
3. Confirm access by pressing the
key.
4. Select the EHC–04 main PCB by pressing the or key.
5. Confirm the selection by pressing the
key.
10 Settings
7685645 - v04 - 07032018
AWHP-2 iMPI