3. Select the number corresponding to the installation type by pressing
the or key. Selecting the installation type enables automatic
configuration of the parameters required for the control panel to op
erate correctly (gradient, maximum circuit temperature, etc.). For a
configuration which differs from those proposed here, press the
h
key on the control panel and configure the parameters manually.
Installation type
No.
One direct heating circuit
01
One direct heating circuit and one domestic hot water
tank
02
One direct heating circuit and one underfloor heating
circuit with mixing valve
03
One direct heating circuit and one domestic hot water
tank and one underfloor heating circuit with mixing
valve
04
One direct underfloor heating circuit
05
One direct underfloor heating circuit and one domestic
hot water tank
06
4. Confirm the selection by pressing the
key.
5. Set the heating curve.
The main parameters are set.
6. Based on the additional options connected, carry out the required
settings.
8.5
Checking the minimum flow
Heating installations must be able to guarantee a minimum flow rate at all
times. If the flow rate is too low, the heat pump may shut itself down for its
own protection; the heating, cooling and domestic hot water functions are
then no longer guaranteed.
1. Check the minimum flow rate as defined by the HP010 parameter.
See
The flow rate value within the installation can be read using the
AM056 parameter.
2. Set the differential pressure valves to guarantee an optimum flow
rate in the installation when thermostatic valves are closed. The opti
mum flow rate is defined by the HP069 parameter.
8.6
Final instructions
The various parameters for the heat pump are pre-set in the factory.
These factory settings are suitable for the most common heating systems.
For other systems and situations, the parameters can be modified.
1. Deactivate the heat pump's domestic hot water mode.
2. Simulate a heat demand to start up heating mode.
3. Check start-up of the outdoor unit and the back-ups connected.
4. Check the flow rate in the installation in comparison to the minimum
flow rate.
5. Put the heat pump in shut-down/frost protection mode.
Fig.77
MW
-1
0
0
0
6
7
6
-1
Fig.78
01
MW-10001142-2
19°
+
02
19°
+
+
03
19°
+
+
04
19°
+
+
+
05
19°
+
06
19°
+
+
8 Commissioning
68
AWHP-2 iMPI