Description of the ADV advanced parameters
Factory setting
EHC–04
Factory setting
SCB-04
AP072
Type of the humidity sensor used
0 =No
1 =OnOff
2 =0-10V sensor
0
AP101
Disable (0) or Enable (1) the de-aeration cycle
0 =Off
1 =Auto
2 =On
1
not available
AP102
Configuration of the boiler pump as zone pump or system pump
(feed lowloss header)
0 =No
1 =Yes
1
not available
HP : Heat-pump Parameters = Heat pump parameters
Tab.45
ADV parameter
Description of the ADV advanced parameters
Factory setting
EHC–04
HP002
Maximum flow temperature of the heat pump without backups
Can be set from 20 °C to 90 °C
65 (6 kW - 8 kW - 11
kW - 16 kW)
60 (4.5 kW)
HP003
Minimum flow temperature allowed in cooling mode
Can be set from 5 °C to 30 °C
5
HP010
Minimum flow rate in heating mode
Can be set from 0 l/m to 90 l/m
5 for 4.5 kW
5 for 6 kW
8 for 8 kW
12 for 11 kW
12 for 16 kW
HP011
Minimum flow rate that triggers a warning message indicating that flow is going
low
Can be set from 0 l/m to 95 l/m
7 for 4.5 kW
7 for 6 kW
9 for 8 kW
14 for 11 kW
14 for 16 kW
HP030
Delay time for starting the next generator (backup stage) in central heating mode
Can be set from 0 Min to 600 Min
0
HP031
Delay time for stopping the next generator (backup stage) in central heating
mode
Can be set from 0 Min to 600 Min
0 = auto mode: use parameters HP047 to HP050
4
HP033
Pulse valency of the external electrical meter (Wh)
Can be set from 0 Wh to 1000 Wh
1
HP034
Capacity first electrical backup stage
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
0
HP035
Capacity second electrical backup stage
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
0
HP036
Rate of glycol added in the evaporator circuit
0 =0% glycol
1 =20% glycol
2 =30% glycol
3 =40% glycol
0
10 Settings
7685645 - v04 - 07032018
AWHP-2 iMPI