Parameter
Description
Factory setting
CIRCA
Factory setting
CIRCB
CP340
Type of Reduced Night Mode, stop or maintain heating of
circuit
0 =
Stop heat demand
1 = Continue heat demand
1
0
CP470
Setting of the screed drying program of the zone
0 = deactivated
Can be set from 1 to 30 days
0
0
CP480
Setting of the start temperature of the screed drying programm
of the zone
Can be set from 20 °C to 50 °C
20
20
CP490
Setting of the stop temperature of the screed drying programm
of the zone
Can be set from 20 to 50 °C
20
20
CP500
Enable/Disable Flow temperature sensor of the zone
0 =Off
1 =On
Do not modify this setting
not available
0
CP640
Opentherm Logic level contact of the zone
0 = contact open for heating demand
1 = contact closed for heating demand
1
1
CP650
Desired reduced room temperature setpoint in cooling mode
per zone
Can be set from 20 °C to 30 °C
29
29
CP690
Reversed Opentherm contact in cooling mode for heat demand
per zone
0 =No
1 =Yes
0
0
CP750
Maximal Zone Preheat time
Can be set from 0 Min to 240 Min
0
0
CP780
Selection of the control strategy for the zone
0 =Extra Slow
1 =Slowest
2 =Slower
3 =Normal
4 =Faster
5 =Fastest
0
0
ADV
Advanced parametersADV
CIRCA sub-menu:
not available
CIRCB sub-menu:
available
10.2.2 Installer \CIRCA and CIRCB\ADV menu
Tab.40
ADV
Description of the ADV advanced parameters
Factory setting
CIRCB
CP330
The time needed by the valve to be fully opened
Can be set from 0 Sec to 240 Sec
Do not modify this setting
60
CP520
Power setpoint per zone
Can be set from 0 % to 100 %
Do not modify this setting
100
10 Settings
78
AWHP-2 iMPI
7685645 - v04 - 07032018