ADV
Description of the ADV advanced parameters
Factory setting
CIRCB
CP530
Pulse Width Modulation pump speed per zone
Can be set from 0 % to 100 %
Do not modify this setting
20
CP730
Selection of heat up speed of the zone
0 =Extra Slow
1 =Slowest
2 =Slower
3 =Normal
4 =Faster
5 =Fastest
Do not modify this setting
2
CP740
Selection of Cool down speed of the zone
0 =Slowest
1 =Slower
2 =Normal
3 =Faster
4 =Fastest
Do not modify this setting
2
CP770
The zone is after a Buffer tank
0 =No
1 =Yes
Do not modify this setting
1
10.2.3 Installer \DHW menu
A domestic hot water sensor must be connected to the EHC–04 board to
display these parameters.
DP : Direct Hot Water Parameters = Domestic hot water tank parameters
Tab.41
Parameter
Description
Factory setting
DP051
Domestic Hot Water ECO or CONFORT setting
0 =ECO (Only HP)
1 =Comfort (HP+Boiler)
0
DP120
Hysteresis temperature relative to the DHW temperature setpoint
Can be set from 0 °C to 40 °C
8
DP130
Offset added on the DHW temperature to obtain the dynamic generator setpoint. 20
DP213
Post run time of the DHW pump/3 way valve after DHW production
Can be set from 0 Min to 99 Min
3
ADV
Advanced parametersADV
10.2.4 Installer \DHW\ADV menu
A domestic hot water sensor must be connected to the EHC–04 board to
display these parameters.
DP : Direct Hot Water Parameters = Domestic hot water tank parameters
10 Settings
7685645 - v04 - 07032018
AWHP-2 iMPI
79