10.2.1 Installer \CIRCA and CIRCB menu
CP : Circuits Parameters = Heating circuit parameters
Tab.39
Parameter
Description
Factory setting
CIRCA
Factory setting
CIRCB
CP000
Maximum Flow Temperature setpoint zone
For circuit A: Can be set from 7 °C to 100 °C
Electrical back-up:
90
Hydraulic back-up:
75
50
CP020
Type of circuit A, connected to the EHC–04 PCB:
0 = heating circuit deactivated
1 = radiators. Cooling not possible.
2 = underfloor heating. Cooling possible.
3 = not available
4 = not used
5 = convection fan. Cooling possible.
Type of circuit B, connected to the SCB-04 PCB:
0 = heating circuit deactivated
1 = radiators. Cooling not possible.
2 = underfloor heating with mixing valve. Cooling possible.
3 =Swimming pool
4 = not used
5 = convection fan. Cooling possible.
6 and above = not used
2
2
CP030
Bandwith of mixing valve zone where modulation takes place.
Can be set from 4 °C to 16 °C
not available
12
CP040
Pump post runtime of the zone
Can be set from 0 Min to 20 Min
3
4
CP050
Can be set from 0 °C to 16 °C
not available
4
CP060
Wished room zone temperature on holiday period
Can be set from 5 °C to 20 °C
6
6
CP070
Max RoomTemperature limit of the circuit in reduced mode,
that allows switching to comfort mode
Can be set from 5 °C to 30 °C
16
16
CP210
Comfort footpoint of the temperature of heat curve of the circuit
can be set from 16 to 90 °C
set to 15 = the curve base temperature is set automatically
and is the same as the room set point temperature
15
15
CP220
Reduced footpoint of the temperature of heat curve of the
circuit
can be set from 6 to 90 °C
set to 15 = the curve base temperature is set automatically
and is the same as the room set point temperature
15
15
CP230
Heating curve temperature gradient of the zone
Can be set from 0 to 4
0.7
0.7
CP240
Adjustment of the influence of the zone room unit
Can be set from 0 to 10
3
3
CP270
Mixing flow temperature setpoint cooling of the zone
Can be set from 11 °C to 23 °C
18
18
10 Settings
7685645 - v04 - 07032018
AWHP-2 iMPI
77