6. Select the auto detection parameter by pressing the or keys.
7. Confirm auto detection by pressing the
key.
The automatic detection function is running.
10.6 Reading out measured values
The measured values are available in the Information menu of the dif
ferent PCBs.
Certain parameters are displayed:
according to certain system configurations,
according to the options, circuits or sensors actually connected.
Tab.69 Choosing the menu
Counters
Selection
Measured values on circuit A
Choose menu EHC-04
Measured values on circuit B
Choose menu SCB04-B
Measured values connected to the
operation of the heat pump
Choose menu EHC-04
Tab.70 Values available (X) in the sub-menus EHC-04, SCB04-B
Parameter
Description
Unit
EHC-04
SCB04-B
AM002
"Silent mode" status
X
AM010
The current pump speed
%
X
AM012
Current main status of the appliance.
See
Control system sequence chapter
X
X
AM014
Current sub status of the appliance.
See
Control system sequence chapter
X
X
AM015
Is the pump running?
X
AM016
Flow temperature of appliance.
°C
X
AM019
Water pressure of the primary circuit.
bar
X
AM027
Instantaneous outside temperature
°C
X
X
AM040
Temperature used for hot water control algorithms.
°C
X
AM056
Wate flow rate in the system
l/min
X
AM091
Seasonal mode active (summer / winter)
0: Winter
1: Frost protection
2: Summer neutral band
3: Summer
X
X
AM101
Internal system flow temperature setpoint
X
CM030
Measure of the Room temperature of the zone
°C
X
X
Fig.119
MW
-1
0
0
0
6
6
6
-1
10 Settings
98
AWHP-2 iMPI
7685645 - v04 - 07032018